DEMAND CONTROL VENTILATION (DCV)
Carbon Dioxide (CO2)-based demand controlled ventilation
(DCV) is increasingly used to modulate outside air ventilation based on
real-time occupancy. Measurement and control technology using CO2 sensors
is quickly evolving to a stage of maturity where cost and reliability
will likely approach that of conventional temperature measurement and
control in the near future. As a result, the use of CO2 as an indoor comfort,
ventilation and air quality control parameter has the potential to become
as common as thermostatic control is today. Like any other control system,
the success of CO2-based DCV application is dependent on how it is engineered,
installed and maintained.
An indoor CO2 contaminant level provides a dynamic measure of the balance
between CO2 generation in the space, representing occupancy, measured
in part per million (ppm) and the amount of low CO2 concentration outside
air introduced for ventilation. The net effect is that it is possible
to use CO2 concentration to determine and control the fresh air dilution
rate in a space on a per person basis.
Carbon Dioxide (CO2) and Demand Control Ventilation
DCV
CO2 is one of the most common gases found in our atmosphere. As a point
of reference, concentration in the center of the Pacific Ocean has been
measured at 366 ppm and this is considered as the lowest concentration found
worldwide. In urban areas, outdoor concentrations have been in the 375
to 450 ppm range,
CO2 is not considered harmful nor a contaminant at the levels of 400 to
2000 ppm normally found in buildings. Perceptions of poor air quality
associated with elevated CO2 levels are more indicative of the buildup
of other contaminants as a result of reduced per person ventilation in
a space rather than the direct effect of CO2. All humans, given a similar
activity level, exhale CO2 at a predictable rate based on occupant age
and activity level. This relationship is described in ASHRAE standard
62. For HVAC applications, CO2 is best used as an indicator for fresh air
ventilation on a per person basis.
The relationship between CO2 production and body odor is that CO2 levels
increase or decrease in relation to human metabolic activity. Since CO2
is a good indicator of human metabolic activity, it could also be used
as a tracer for other human emitted bio effluents. High levels of CO2 can
cause nausea, headaches and dizziness. Adults usually can tolerate CO2
concentration of 1,000 ppm, and children usually can tolerate 500 ppm.
Outside air dampers should open to allow enough air to enter a building
to keep the CO2 level below 1,000 ppm.
As this technology has developed, so have codes and standards. The International
Mechanical Code (IMC), the mechanical code of reference for most local
building code bodies in the United States, has included provisions for
CO2-based DCV. IMC codes states that “The minimum flow rate of the
outdoor air that the ventilation system should be capable of supplying
during its operation shall be permitted to be used on the rate per person
indicated in their standard and the actual number of occupants present.”
Also ASHRAE standard 62 has clarified the use of CO2 as a parameter that
can be used for controlling ventilation based on actual real-time occupancy
while still maintaining target cfm-per-person ventilation rates.
BENEFITS OF CO2-BASED DEMAND CONTROL VENTILATION
DCV
CO2– based DCV does not affect the design ventilation capacity
required to serve the space; it just controls the operation of the system
to be more in tune with how a building actually operates.
Excessive over-ventilation is avoided while still maintaining good Indoor
Air Quality (IAQ) and providing the required cfm-per-person outside air
requirement specified by codes and standards. The ASHRAE Technical Committee
has observed operational energy savings. This observation has been verified
in a recent literature review on CO2 control that cited studies where
energy savings form DCV control approaches ranged from 5% to 80% versus
a fixed ventilation strategy. System paybacks can range from a few months
to two years and are often substantial enough to help pay for other system
or building upgrades.
The payback from CO2–based DCV will be greatest in higher density
spaces that are subject to variable or intermittent occupancy that would
have normally used a fixed ventilation strategy (e.g., theaters, schools,
retail establishments, meeting and conference areas).
In spaces with more static occupancies (e.g. offices), CO2–based
DCV can provide control and verification that adequate ventilation is
providing to all spaces. For example, a building operator may arbitrarily
and accidentally establish a fixed air intake damper position that results
in over or under ventilation of all or parts of a space. A CO2 control
strategy can ensure the position of the intake air dampers is appropriate
for the ventilation needs and occupancy of the ventilated space at all
times. This may save additional energy when outside air intakes are arbitrarily
set to over-ventilation.
In some buildings, infiltration air or open windows may be a significant
source of outside air. A CO2 sensor will consider the contribution of
infiltration in a space and only require the mechanical system to make
up what is necessary to meet required ventilation levels. The savings
are in addition to those quoted earlier.
When integrated with the appropriate building control strategy, ventilation
can be controlled zone by zone based on actual occupancy. This allows
for the use of supply air from under-occupied zones to be redistributed
to areas where more ventilation or cooling is needed.
A CO2 control strategy can be issued to maintain any per-person ventilation
rate. As a result this approach is highly adaptable to changing building
uses and any changes that may occur in future recommended ventilation
rates.
(For more information on DCV Controller, please click ET-858
product).
DESIGN/INSTALLATION RECOMMENDED GUIDELINES
General Guidelines
The objective of a CO2 control strategy is to modulate ventilation to
maintain target cfm/person ventilation rates based on actual occupancy.
The strategy should allow for reduced overall ventilation during periods
of occupancy that are less than full occupancy and as a result save energy.
Typical control approaches have used a proportional control algorithm
to modulate ventilation between a base ventilation rate established non-occupant-related
sources and the design ventilation rate for the space. Modulation of outside
air above base ventilation begins when indoor CO2 is above the high limit
set by the CO2 sensor. The outdoor damper OA modulates above the minimum
setting of the OA damper.
Duct mounted CO2 sensors are best used where a single space or when multiple
spaces with common occupancy patterns are being ventilated. The most common
area of installation is directly in the return air ductwork or inside
the return air plenum.
Wall mounted CO2 sensors are recommended for multiple units installation
where the return air may not be representative of what is actually happening
in the particular space.
In setting the minimum outdoor damper, ventilation rates should not be
reduced below 20% to 50% of design. Maintaining this minimum rate supplies
sufficient ventilation air to dilute building contaminant sources, even
at low occupancy levels.
Most of the CO2 sensors have analog output of 0-10 VDC or 4-20mA correspond
to 0-2000 ppm CO2 concentration. Setting values of the CO2 level on the
economizer/IAQ controller should be based on the difference between the
maximum designed outside air and the minimum setting on the OA damper.
When to Use Outdoor Air CO2 Sensing
CO2-based demand controlled ventilation is based on the principle that
the differential between inside and outside concentrations can give an
indication of the ventilation requirement rate in the space. As a general
rule of thumb, an inside/outside differential of 700 ppm is indicative
of a ventilation rate of 15cfm/person (7 L/s). An inside/outside differential
of 500 ppm is indicative of a 20 cfm/person (9 L/s) ventilation rate.
For most applications, outside air can be assumed to be at 400±50
ppm. As a result most control strategies will work well if the designer
or installer assumes outside levels are at 400 ppm. Even if outside concentrations
are higher than 500 ppm, and 400 ppm is used as the assumed outside level,
the only impact will be that the space will be slightly over ventilated
by about 2 cfm/person (0.9 L/s) during those periods when outside levers
are elevated. Since the lowest levels are approximately 366 ppm, a conservative
maximum under-ventilation effect of assuming a 400-ppm outside level is
less than 1 cfm per person (0.47 L/s).
Elevated outside CO2 levels are generally due to the presence of localized
combustion sources such as vehicles, power plants, or building exhausts.
If elevated levels are measured, it may be a function of the location
of outside air intakes related to localized combustion sources. In these
applications and if deemed necessary by the designer, CO2 sensors are
installed outdoor to ensure that ventilation rates are controlled based
on real-time differential between inside and outside CO2 concentrations.
Setting of the Outdoor Air Damper for the Minimum
Outside Air
By knowing the temperature of the outside air and the temperature of the
return air, you can determine the temperature of the mixed air that enters
the inlet side of the supply blower. Use the following equation:
MAT= (OAT x %OA) + (RAT x %RA)
Where
MAT = mixed air temperature
OAT = outside air temperature
%OA = % of outside temperature
RAT = return air temperature
%RA = % of return air volume
Let’s say that the temperature of the return air is 80†F, and that
the temperature of the outside air is 40†F. Assume that you’re working
on a building that requires a mixture of 10% outside air and 90% return
air. Then:
MAT = (40†F x 0.1) + (80†F x 0.9)
= 4 + 72
= 76†F
Now you know that the temperature of the mixed air should be 76†F.
If you are commissioning a 10-ton unit that moves 4,000 cfm of air, you
also know that you want about 400 cfm of outside air (10% of 4,000).
Measure the temperature of the air at the blower inlet. If the mixed air
temperature is above 76†F, then the amount of outside air is less than
10%, or 400 cfm. If the mixed air temperature is below 76†F, then the
amount of outside air is more than 10%, or 400 cfm. In either case, you
can adjust the dampers accordingly. Within a short period of time, you
can take another temperature reading to determine whether the dampers
have been adjusted properly.