Why Compressors Fail
Compressor failure is a common problem in the HVAC&R
industry. It inconveniences suppliers and customers as well as costing
time and money. The two basic causes of compressor failure are: an incorrect
or non-diagnosis and improper installation or maintenance of the compressor.
Very often, a compressor fails because of an external problem. More than
60 percent of all failures are caused by system and service-related problems.
Yet more often than not, a compressor will be replaced without the service
person determining the actual cause of the failure. As expected under
such circumstances, the new compressor will eventually fail as well at
rate several times higher than for original installation.
For the majority of compressors, which do not fail in 15 years, there
must be a condition of part variation that withstands all of the applied
operating conditions. Other compressors with more serious variations eventually
experience the operating condition that will cause failure. Compressors,
operated within their limits, do not wear out. In one documented instance,
a compressor ran more than 30,000 hours and 16,000 cycles. When it was
subsequently torn down and all its parts were measured, they were found
to be still within new compressor specifications and tolerances.
Then why do compressors fail? Two extreme cases may lead to a general
conclusion. First, a compressor can be subjected to abusive conditions,
such as a harsh tropical environment. Extremes of temperature or pressure
can eventually make any compressor fail. Other potential abuse situations
would include a loss of oil and/or a loss of refrigerant charge. Secondly,
a compressor can contain a gross manufacturing defect.
Compressors fail because of: a loss of Lubrication; flooding; flooded
starts; slugging; contamination; overheating; and/or electrical problems.
Oil does not return at a satisfactory rate when there is: a low, refrigerant
velocity, short cycling, low load, traps or piping errors.
Airside problems are known to be a significant cause of flooding. They
include broken evaporator fan belts, bad fan motors, dirty coils, and
dirty filters. A dirty condenser coil or a failed condenser fan motor
allows heat to build in the coil rather than being rejected into the atmosphere.
The compressor then has to pump against excessive pressure, which may
cause it to overheat, resulting in accelerated component wear, damage,
or complete failure
One method of minimizing refrigerant accumulation in the compressor, or
a flooded start, is to incorporate a pump down control system. In this
system a solenoid valve can be installed in the liquid line. The compressor
pumps down the system and a low-pressure switch stops the compressor after
the refrigerant has been removed from the low side of the system. The
compressor restarts, after a time delay, when the thermostat energizes
the solenoid valve again.
Unbalance of voltage and/or current can lead to electrical problems, which
in turn causes compressor failure. Both voltage and current anomalies
cause an increase in temperature, which may go unnoticed for a long period
of time.
There are several things that can be done to help prevent repeat compressor
failures, such as: improving equipment maintenance and record keeping;
using proper start-up procedures; improving systems and diagnostic skills;
and inspecting the failed compressors. A proper diagnosis as to the cause
of the failure is also essential.
As mentioned previously, compressors are designed to handle normal thermal
temperature gain. However, when they are operated outside their design
conditions, careful attention has to be taken to avoid reduced life expectancy
and potential damage.
If the equipment/systems do not have proper operating and safety protection
and monitoring devices, problems can go undetected until the compressor
burns out.
Cost-effective operation and maintenance require implementing new technology,
installing electronic protective devices to monitor and to warn about
the repeated tripping of the compressor.
(For more information on Compressor Safety Controller, please
click ETCLO-830)